Technical Details
Ice is built and stored in large holding tanks using chillers providing chilled water / glycol at -5ºC. A skid mounted Heat Exchanger provides the interface between the melted ice water from the tank and the customers water / glycol cooling system. When emergency cooling is required, pumps circulate the melted ice water through the heat exchanger satisfying the customers 1.8MW load (per system) for 10 minutes. There are 22 systems employed in the data centre.
General Features:
24 000 litre GRP ice bank
3 x 15kW pumps (2 Run + 1 Stand by)
Gasketed brazed plate heat exchanger
Independent flow monitoring for each major component
Energy efficient ‘when needed’ chiller control
Stainless Steel 316 tubing throughout
Full programmable logic control and communication to BMS via MODBUS
Independent control panel per system