Technical Details
2 off 40kW e3 units
Nominal cooling capacity of 40kW at 10ºC delta T
8 off axial fans diameter 946, 700 rpm and 2.2kW each output power
2 off heat exchangers in copper tube and aluminium fins and galvanised case material
Integral circulation pump, control panel and fan motor isolators
Designed for water glycol (30% mix), fluid entry temp of 16.5°C, fluid flow of 25 litres per second
Pump – single end suction circulation pump
Electrical panel – contains motor starter for pump, temperature control system, PLC & fault indication
Dimensions:
Length: 4,790mm
Width: 2,400mm
Height: 2,415mm
Dry Weight: 2,072Kg
Operative Weight: 2,332Kg